LPM/LPX1000 Series
The LP 1000 Series wet/wet differential pressure transmitter is ideally suited for use in clean room HVAC monitoring and control. The device offers several improvements over traditional sensors such as user accessible damping, excellent long term stability, and wet/wet differential operation where conductive fluids may be exposed to the measurement diaphragms. For applications where the pressure transmitter will be installed within one of the pressure zones, the LPM/LPX 1000 is available in a wet/wet gauge pressure configuration where the second pressure port is eliminated, byventing the sensor directly to the atmosphere.The LP 1000 Series wet/wet differential pressure transmitter is ideally suited for use in clean-room HVAC monitoring and control.
Features
- Ranges ±0.1 to ±30 inH2O (0.25 to 70 m bar)
- Accuracy: ±0.5% FS BSL (±0.25% FS optional)
- Long term stability: > ±0.5% FS / Year
- Calibration certificate option
- Wet/wet differentialpressure
- User accessible damping
- Unidirectional or bidirectional operation
- Current or voltage output
Specifications
Pressure Measurement
Operating Ranges | 0.1, 0.2, 0.25, 0.5, 0.75, 1, 2, 2.5, 3, 4, 5, 6, 8, 10, 16, 20 inH2O and 1 psi unidirectional and bidirectional (other pressure units available, see ordering information). |
---|---|
Overpressure |
|
Maximum Static (Line) Pressure | 30 psi for all ranges |
Electrical Supply Voltage |
Power
Supply (Vs) (at the
terminals) Current output without display 10 to 30 VDC Current output with display 15 to 30 VDC Current output with display and LED indicators 20 to 30 VDC Voltage output 10 to 30 VDC Voltage output (0 to 10 VDC) 15 to 30 VDC
Power Supply
Intrinsically Safe Units
|
Output Signal Option |
Unidirectional Voltage 0 to 2.5 VDC 0 to 5 VDC 0 to 10 VDC 1 to 6 VDC
Current Bidirectional Current Note: voltage outputs are three wire, current outputs are two wire. |
Zero Offset Adjustment | ±5% FS |
Span Adjustment | ±5% FS |
Response Time | User-adjustable 10 ms to 2 s (factory default setting 10 ms) |
Load Impedance | Voltage output 5 kΩ minimum Current output RL (kΩ) < (Vsupply - Vs) 20 |
Performance
Combined Effects of Non-linearity, Hysteresis and Repeatability | ±0.5% FS Best Straight Line (BSL ) ±0.25% FS BSL (optional) |
---|---|
Static Pressure Effects | Effects may be zeroed out at operating line pressure |
Stability | At standard conditions will not change by more than 1% FS averaged over one year |
Supply Sensitivity | <0.05% FS per volt |
Compensated Temperature Range | 32 to 122° F (0 to 50° C) |
Temperature Effects |
Over
the range 32 to 122 °F
(0 to 50° C)
|
Environmental
Protection | Type 3 IP 64 (Except with C2 screw terminals) |
---|---|
Temperature Range | Operating 32 to 122 °F (0 to 50 °C) |
Humidity | 0 to 100% RH, non condensing. |
Mounting Position Effect |
No
effect on span, possible
zero shift correctable
by potentiometer
adjustment. Note: Factory calibrated with diaphragm in the vertical plane. |
Physical
Housing | Aluminum |
---|---|
Wetted Parts | Gases and liquids compatible with aluminum, stainless steel 316L, beryllium copper, brass, Inconel X750, adhesives and plastics. |
Electrical Connection |
|
Pressure Connection | 10-32 UNF female to 0.125 in (3.175 mm) barbed fitting |
Weight: | 1 to 2 lb (0.45 to 0.91 kg) approx depending upon configuration |
Certifications | CE marked ATEX Intrinsically Safe (optional, on current output model only) LCIE05ATEX6081X |
Download
说明 | English | Deutsch | Italiano | Português | Español |
---|---|---|---|---|---|
LPM/LPX1000 Series Brochure |